Mfg Part Number: 3H900 35 11 | Alternate P/N: 3H9003511 | NSN : 5925-00-241-9774 |
NIIN : 002419774 | CAGE Code : 79500 | Manufacturer: Westinghouse Electric Corp |
Item Name : Circuit Breaker | FSC : 5925 Circuit Breakers |
Thank you for choosing to rely on NSN 3Sixty for NSN part 3H900 35 11 and FSC 5925 Circuit Breakers under Circuit Breaker under NIIN 002419774 with. You have reached our NSN RFQ Page where you can request quotes for our most top-requested NSN 5925-00-241-9774 components such as Circuit Breaker manufactured by Westinghouse Electric Corp with CAGE Code 79500. Some of the products we have in stock include part number 3H900 35 11, and various others NSN parts, those of which have been thoroughly assessed for quality and functionality. At NSN 3Sixty, we distinguish ourselves from other distributors in our steadfast commitment to providing person-to-person communication at every stage of the procurement process, offering rapid turnaround times, unmatched cost savings, and exceptional customer service.
NSN 3Sixty receives praise for making quality the cornerstone of its operations, ensuring that our customers never have to worry about the integrity of our products. The NSN 5925-00-241-9774 products that we feature by Westinghouse Electric Corp are paired alongside their corresponding CAGE Code 79500. Furthermore, the NSN items we carry are thoroughly assessed for reliability and authenticity. Get part 3H900 35 11 that suits your operations, we invite you to fill out and submit an RFQ form for your comparisons. For additional questions, you can call or email us directly; we are available 24/7x365!
MRC | Criteria | Characteristic |
---|---|---|
ABHP | OVERALL LENGTH | 6.000 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 3.969 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 4.125 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.188 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 35.0 AMPERES AC ALL LOCATIONS AND 35.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS AND 125.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS AND 5000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 120.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 3600.000 NOMINAL AT 125 PCT ALL LOCATIONS AND 110.000 NOMINAL AT 200 PCT ALL LOCATIONS AND 23.000 NOMINAL AT 300 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |